Fire Fighting Design Basis Report PDF 2022

advertisement

Fire Fighting Design Basis Report PDF

System of fire protection: - The Hydrant System - Watering system. - Flooding system. - Pump sets for fighting fires. - Fire extinguishers and portable first aid kits. - Electrical Panel Automatic Fire Extinguishers - Photoluminescent warning signs. - Fire-resistant sealant. - Fire detection and alarm system of the analogue type.

Fire Fighting Design Basis Report PDF 2022
Fire Fighting Design Basis Report PDF 2022


Electrically powered jockey pumps and fire pumps will draw water from fire reserve tanks. There is a standby diesel engine driven pump for fire hydrants, deluge system, and sprinkler system. Each pump has its own suction line from the suction header, and delivery is linked to the system. Pumps' function is to keep the farthest hydrant at 3.5 Kg/Sq.cm. According to fire regulations, the diesel engine driven fire pump must have the same capacity as the electrically operated fire hydrant / sprinkler pump. This pump is activated in the event of a total power outage or an electrical pump failure. The Jockey pump is used intermittently to compensate for hydraulic losses in the system and to maintain the minimum pressure.

advertisement

Pumps:

- 1 No. Main Pump (For Hydrant/Sprinkler), 273 M3/Hr, Head 71 m Pump Operated by Electricity

- 1 No. Standby Pump, 273 M3/Hr, Head 88 m - Diesel Engine Driven Pump

- 1 No. Jockey Pump Set, 10.8 M3/Hr, Head 71 m

System of Fire Hydrants:

The Plant must have a separate fire hydrant riser connected to the hydrant landing valve, as well as a fire hose cabinet with swinging hose reels, a fire man's axe, 63 mm dia canvas hose, and nozzles. A fire fighting ring main shall be installed around the Plant. External yard hydrants must be spaced at 30 metre intervals. At these yard hydrants, the necessary hose pipe and nozzle must be stored in a closed cabinet with glass shutters.

Contents in Fire Fighting Design Basis Report PDF 2022

advertisement

1. SCOPE OF WORK 4

2. FIRE PROTECTION & DETECTION SYSTEM 5

3. SPECIFICATION & MAKES 12 DOC. NO.- 100-1101-L1L-R00 GAJANAN AND SONS CLIENT:FIRE SAFETY PVT. LTD. Rev –0 M/s KDL 120MW COMBINED CYCLE POWER PLANT PROJECT SHEET NO 3 of 12

While making this DBR, following regulations are considered NFPA 10 portable Fire Extinguisher

NFPA 12 Carbon Dioxide Extinguishing Systems

NFPA 13 sprinklers

NFPA 14 Installation of Standpipe, private Hydrants, and Hose System

NFPA 15 Water Spray fixed system for fire Protection

NFPA 24 Yard hydrants

NFPA 30 Flammable and combustible Liquids Code

NFPA 70 National Electrical Codes

NFPA 72D9E National fire Alarm Code

NFPA 850 Recommended Practice for Fire Protection for Eclectic Generating plants and High Voltage Direct Current Converters Stations.

ANSI B31.1 Power Piping

ASME VIII Pressure Tank